B089: Monitor display select for networked inverter – When the X200 inverter is

controlled via network, the inverter’s keypad display can still provide Monitor Mode.
The D00x parameter selected by function B089 sill be displayed on the keypad. See

“Local Monitoring During Network Operation” on page 3-8

for more details.

B092: Cooling Fan Control – You can select the performance of the cooling fan (if your
inverter has the fan) whether it stops or keep on running, after the inverter stops the

motor. This can result in an additional energy saving.

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

Monitor display select for

networked inverter

B089

PANEL

d001

Selects the parameter displayed on the

keypad display when the inverter is

networked, 7 options:
01

…Output frequency monitor

02

…Output current monitor

03

…Rotation direction monitor

04

…Process variable (PV), PID

feedback monitor

05

…Intelligent input terminal status

06

…Intelligent output terminal status

07

…Scaled output frequency monitor

9

01

01

Cooling fan control

B092

FAN-CTRL

OFF

Selects when the fan is ON per inverter

operation, three options:
00

…Fan is always ON

01

…Fan is ON during run, OFF during

stop (5 min. delay from ON to OFF)

02

…Fan is temperature controlled

U

00

00

344

Confi

guri

ng Driv

e

Parameters