Monitoring trip events, history, & conditions -5, Monitoring trip events, history, & conditions – Hitachi X200 Series User Manual

Page 208

Advertising
background image

Monitoring Trip Events, History, & Conditions

Fault Detection and Clearing

The microprocessor in the inverter detects a variety

of fault conditions and captures the event,
recording it in a history table. The inverter output

turns OFF, or “trips” similar to the way a circuit

breaker trips due to an over-current condition.
Most faults occur when the motor is running (refer

to the diagram to the right). However, the inverter

could have an internal fault and trip in Stop Mode.
In either case, you can clear the fault by pressing the Stop/Reset key. Additionally, you

can clear the inverter’s cumulative trip history by performing the procedure

Restoring

Factory Default Settings” on page 6–8

(setting B084=00 will clear the trip history but

leave inverter settings intact).

Error Codes

An error code will appear on the display automatically when a fault causes the inverter

to trip. The following table lists the cause associated with the error.

Error

Code

Name

Cause(s)

E 01

Over-current event while at

constant speed

E 02

Over-current event during

deceleration

E 03

Over-current event during

acceleration

E 04

Over-current event during

other conditions

The inverter output was short-circuited, or the

motor shaft is locked or has a heavy load. These

conditions cause excessive current for the inverter,

so the inverter output is turned OFF.
The dual-voltage motor is wired incorrectly.

E 05

Overload protection

When a motor overload is detected by the electronic

thermal function, the inverter trips and turns OFF
its output.

E 07

Over-voltage protection

When the DC bus voltage exceeds a threshold, due

to regenerative energy from the motor.

E 08

EEPROM error

When the built-in EEPROM memory has problems

due to noise or excessive temperature, the inverter
trips and turns OFF its output to the motor.

E 09

Under-voltage error

A decrease of internal DC bus voltage below a
threshold results in a control circuit fault. This

condition can also generate excessive motor heat or

cause low torque. The inverter trips and turns OFF
its output.

E 11

CPU error

A malfunction in the built-in CPU has occurred, so

the inverter trips and turns OFF its output to the
motor.

E 12

External trip

A signal on an intelligent input terminal configured
as EXT has occurred. The inverter trips and turns

OFF the output to the motor.

Run

Stop

RUN

STOP
RESET

Trip

STOP
RESET

Fault

Fault

65

T

roub

lesh

ooting

an

d

Mainte

nanc

e

Advertising