The following table lists the holding registers for the “A” Group Standard Functions.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A001 Frequency source

setting

R/W Five options; select codes:

00...Keypad potentiometer
01...Control terminal

02...Function F001 setting

03...ModBus network input
10...Calculate function output

1019h

0 to 3, 10

A002 Run command source

setting

R/W Three options; select codes:

01...Control terminal
02...Run key on keypad, or

digital operator

03...ModBus network input

101Ah

1, 2, 3

A003 Base frequency setting R/W Settable from 30 Hz to the

maximum frequency

101Bh 30 to max.

freq.

1 Hz

A203 Base frequency setting,

2nd motor

R/W Settable from 30 Hz to the 2nd

maximum frequency

150Ch 30 to max.

freq.2

1 Hz

A004 Maximum frequency

setting

R/W Settable from the base frequency

up to 400 Hz

101Ch 30 to 400

1 Hz

A204 Maximum frequency

setting, 2nd motor

R/W Settable from the 2nd base

frequency up to 400 Hz

150Dh 30 to 400

1 Hz

A005 [AT] selection

R/W Five options, select codes:

00... Select between [O] and [OI]

at [AT]

02... Select between [O] and

keypad potentiometer

03... Select between [OI] and

keypad potentiometer
04... Only [O] input active

05... Only [OI] input active

101Dh

0, 2, 3,

4, 5

A011 O–L input active range

start frequency

R/W The output frequency

corresponding to the analog

input range starting point,
Range is 0.0 to 400.0

1020h

0 to 4000

0.1 Hz

A012 O–L input active range

end frequency

R/W The output frequency

corresponding to the analog
input range ending point, range

is 0.0 to 400.0

1022h

0 to 4000

0.1 Hz

A013 O–L input active range

start voltage

R/W The starting point (offset) for the

active analog input range, range

is 0. to 100

1023h

0 to 100

1 %

A014 O–L input active range

end voltage

R/W The ending point (offset) for the

active analog input range, range
is 0. to 100.

1024h

0 to 100

1 %

A015 O–L input start

frequency enable

R/W Two options; select codes:

00...Use offset (A011 value)

01...Use 0 Hz

1025h

0, 1

A016 External frequency

filter time constant

R/W Range n = 1 to 16, where n =

number of samples for average.

Set 17 to use 16-samples for avg.,

plus deadband +0.1/-0.2Hz

1026h

1 to 17 1 sample

B25