The alarm relay output can be configured in two main ways:

Trip/Power Loss Alarm – The alarm relay is configured as normally closed
(C036=1) by default, shown below (left). An external alarm circuit that detects

broken wiring also as an alarm connects to [AL0] and [AL1]. After powerup and

short delay (< 2 seconds), the relay energizes and the alarm circuit is OFF. Then,
either an inverter trip event or an inverter power loss will de-energize the relay

and open the alarm circuit

Trip Alarm – Alternatively, you can configure the relay as normally open (C036=0),

shown below (right). An external alarm circuit that detects broken wiring also as

an alarm connects to [AL0] and [AL2]. After powerup, the relay energizes only
when an inverter trip event occurs, opening the alarm circuit. However, in this

configuration, an inverter power loss does not open the alarm circuit.

Be sure to use the relay configuration that is appropriate for your system design. Note
that the external circuits shown assume that a closed circuit = no alarm condition (so

that a broken wire also causes an alarm). However, some systems may require a closed

circuit = alarm condition. In that case, then use the opposite terminal [AL1] or [AL2]
from the ones shown.

N.C. contacts (C036=01)

N.O. contacts (C036=00)

During normal operation When an alarm occurs or

when power is OFF

During normal operation

or when power is OFF

When an alarm occurs

Power

Run Mode

AL0-AL1

AL0-AL2

Power

Run Mode

AL0-AL1

AL0-AL2

ON

Normal

Closed

Open

ON

Normal

Open

Closed

ON

Trip

Open

Closed

ON

Trip

Closed

Open

OFF

Open

Closed

OFF

Open

Closed

AL1

Power
supply

Load

AL0

AL2

AL1

Power
supply

Load

AL0

AL2

AL1

Power
supply

Load

AL0

AL2

AL1

Power
supply

Load

AL0

AL2

443

Operatio

ns and

Monitori

ng