B − 13 – Hitachi X200 Series User Manual

Page 240

Advertising
background image

Write in Holding Register [06h]:

This function writes data in a specified holding register. An example follows:
• Write “50Hz” as the first Multi-speed 0 (A020) in an inverter having slave address

“5.”

• This example uses change data “500(1F4h)” to set “50Hz” as the data resolution of

the register “1029h” holding the first Multi-speed 0 (A020) is 0.1Hz

Query:

Response:

No.

Field Name

Example

(Hex)

No.

Field Name

Example

(Hex)

1

Slave address *1

08

1

Slave address

08

2

Function code

06

2

Function code

06

3

Register start address

*2

(high order)

10

3

Register start address

*2

(high order)

10

4

Register start address

*2

(low order)

28

4

Register start address

*2

(low order)

28

5

Change data

(high order)

01

5

Change data

(high order)

01

6

Change data

(low order)

F4

6

Change data

(low order)

F4

7

CRC-16 (high order)

0D

7

CRC-16 (high order)

0D

8

CRC-16 (low order)

8C

8

CRC-16 (low order)

8C

Note 1:

No response is made for a broadcasting query.

Note 2:

The PDU Register Number are addressed starting at zero. Therefore register

numbered “1029h” are addressed as “1028h”. Register address value

(transmitted on Modbus line) is 1 less than the Register Number.

When writing in a selected holding register fails, see the exception response.

B13