background image

4.

Take measures to minimize interference that is frequently coupled in through

installation cables.

Separate interfering cables with 0.25m minimum from cables susceptible to

interference. A particularly critical point is laying parallel cables over longer

distances. If two cables intersect (one crosses over the other), the interference is
smallest if they intersect at an angle of 90°. Cables susceptible to interference

should therefore only intersect motor cables, intermediate circuit cables, or the

wiring of a rheostat at right angles and never be laid parallel to them over
longer distances.

5.

Minimize the distance between an interference source and an interference sink

(interference- threatened device), thereby decreasing the effect of the emitted

interference on the interference sink.

You should use only interference-free devices and maintain a minimum distance

of 0.25 m from the adjustable frequency inverter.

6.

Follow safety measures in the filter installation.

If using external EMC filter, ensure that the ground terminal (PE) of the filter is

properly connected to the ground terminal of the adjustable frequency inverter.

An HF ground connection via metal contact between the housings of the filter

and the adjustable frequency inverter, or solely via cable shield, is not permitted
as a protective conductor connection. The filter must be solidly and permanently

connected with the ground potential so as to preclude the danger of electric

shock upon touching the filter if a fault occurs.

To achieve a protective ground connection for the filter:

Ground the filter with a conductor of at least 10 mm

2

cross-sectional area.

Connect a second grounding conductor, using a separate grounding terminal

parallel to the protective conductor. (The cross section of each single protective

conductor terminal must be sized for the required nominal load.)

Integrated EMC Filter

The X200 series inverters for European market (-SFE, and HFE models) have

integrated filter complies to EN61800-3 as shown below.

200V class (-SFE models) – EN61800-3 category C1

400V class (-HFE models) – EN61800-3 category C2

Please refer to the next page for the installation.