B − 32 – Hitachi X200 Series User Manual

Page 259

Advertising
background image

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

B021 Overload restriction

operation mode

R/W

10B5h

B221 Overload restriction

operation mode, 2nd

motor

Select the operation mode during

overload conditions, three

options, option codes:
00

…Disables

01

…Enabled for acceleration and

constant speed

02

…Enabled for constant speed

only

1529h

0, 1, 2

B022 Overload restriction

level setting

R/W

10B6h

B222 Overload restriction

level setting, 2nd

motor

R/W

Sets the level for overload

restriction, between 20% and

150% of the rated current of the
inverter, setting resolution is 1%

of rated current

152Ah

2000 to

15000

0.01%

B023 Deceleration rate at

overload restriction

R/W

10B7h

B223 Deceleration rate at

overload restriction,

2nd motor

R/W

Sets the deceleration rate when

inverter detects overload, range

is 0.1 to 30.0, resolution 0.1

152Bh

1 to 300

0.1 sec

B028 Source of overload

restriction selection

R/W Two option codes:

00

…set value of B022

01

…[O] input

10BBh

B228 Source of overload

restriction selection,

2nd motor

R/W Two option codes:

00

…set value of B222

01

…[O] input

152Ch

0, 1

B029 Deceleration rate of

frequency pull-in
restart setting

R/W Sets the deceleration rate when

frequency pull-in restart, range
is 0.1 to 3000.0, resolution 0.1

1171h 1 to 30000 0.1 sec

B030 Current level of

frequency pull-in

restart setting

R/W Sets the current level of

frequency pull-in restart, range

is 0.2*inverter rated current to

2.0*inverter rated current,

resolution 0.1

1172h

200 to
20000

0.01%

B031 Software lock mode

selection

R/W Prevents parameter changes, in

four options, option codes:
00

…all parameters except B031

are locked when [SFT]
terminal is ON

01

…all parameters except B031

and output frequency F001

are locked when [SFT]

terminal is ON

02

…all parameters except B031

are locked

03

…all parameters except B031

and output frequency F001
are locked

10

…High level access including

B031

10BCh

0, 1, 2, 3

B050 Selection of the non

stop operation

R/W Two option codes:

00

…Disabled

01

…Enabled

10C9h

0, 1

B051 Non stop operation

start voltage setting

R/W Setting of DC bus voltage to start

non stop operation. Range is 0.0

to 1000.0

10CAh 0 to 10000

0.1 V

B32

Appe

ndix B