B − 32 – Hitachi X200 Series User Manual
Page 259
![background image](/manuals/96512/259/background.png)
List of Holding Registers
Network Data
Func.
Code
Name
R/W
Description
Reg.
Range
Res.
B021 Overload restriction
operation mode
R/W
10B5h
B221 Overload restriction
operation mode, 2nd
motor
Select the operation mode during
overload conditions, three
options, option codes:
00
…Disables
01
…Enabled for acceleration and
constant speed
02
…Enabled for constant speed
only
1529h
0, 1, 2
−
B022 Overload restriction
level setting
R/W
10B6h
B222 Overload restriction
level setting, 2nd
motor
R/W
Sets the level for overload
restriction, between 20% and
150% of the rated current of the
inverter, setting resolution is 1%
of rated current
152Ah
2000 to
15000
0.01%
B023 Deceleration rate at
overload restriction
R/W
10B7h
B223 Deceleration rate at
overload restriction,
2nd motor
R/W
Sets the deceleration rate when
inverter detects overload, range
is 0.1 to 30.0, resolution 0.1
152Bh
1 to 300
0.1 sec
B028 Source of overload
restriction selection
R/W Two option codes:
00
…set value of B022
01
…[O] input
10BBh
B228 Source of overload
restriction selection,
2nd motor
R/W Two option codes:
00
…set value of B222
01
…[O] input
152Ch
0, 1
−
B029 Deceleration rate of
frequency pull-in
restart setting
R/W Sets the deceleration rate when
frequency pull-in restart, range
is 0.1 to 3000.0, resolution 0.1
1171h 1 to 30000 0.1 sec
B030 Current level of
frequency pull-in
restart setting
R/W Sets the current level of
frequency pull-in restart, range
is 0.2*inverter rated current to
2.0*inverter rated current,
resolution 0.1
1172h
200 to
20000
0.01%
B031 Software lock mode
selection
R/W Prevents parameter changes, in
four options, option codes:
00
…all parameters except B031
are locked when [SFT]
terminal is ON
01
…all parameters except B031
and output frequency F001
are locked when [SFT]
terminal is ON
02
…all parameters except B031
are locked
03
…all parameters except B031
and output frequency F001
are locked
10
…High level access including
B031
10BCh
0, 1, 2, 3
−
B050 Selection of the non
stop operation
R/W Two option codes:
00
…Disabled
01
…Enabled
10C9h
0, 1
−
B051 Non stop operation
start voltage setting
R/W Setting of DC bus voltage to start
non stop operation. Range is 0.0
to 1000.0
10CAh 0 to 10000
0.1 V
B−32
Appe
ndix B