Free-run Stop

When the terminal [FRS] is turned ON, the inverter stops the output and the motor

enters the free-run state (coasting). If terminal [FRS] is turned OFF, the output
resumes sending power to the motor if the Run command is still active. The free-run

stop feature works with other parameters to provide flexibility in stopping and starting

motor rotation.

In the figure below, parameter B088 selects whether the inverter resumes operation

from 0 Hz (left graph) or the current motor rotation speed (right graph) when the [FRS]

terminal turns OFF. The application determines the best setting.

Parameter B003 specifies a delay time before resuming operation from a free-run stop.

To disable this feature, use a zero delay time.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Causes output to turn OFF, allowing motor to free

run (coast) to stop

11

FRS

Free-run Stop

OFF Output operates normally, so controlled

deceleration and stops motor

Valid for inputs:

C001~C005

Required settings

B003, B088, C011 to C015

Notes:
• When you want the [FRS] terminal to be active

low (normally closed logic), change the setting

(C011 to C015) that corresponds to the input

(C001 to C005) that is assigned the [FRS]
function.

Example (requires input configuration—
see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L

PCS P24

FRS

[FRS]

1

0

Motor speed

t

[FW,RV]

1

0

Zero frequency start

B088 = 00

[FRS]

1

0

Motor speed

t

[FW,RV]

1

0

Resume from motor speed

B088 = 01

B003

Wait time

418