DC Bus AVR for deceleration Settings

This function is to achieve stable DC bus voltage in case of deceleration. DC bus voltage

raises due to regeneration during deceleration. When this function is activated
(B133=01), inverter controls the deceleration time so that the DC bus voltage not to go

up to the overvoltage trip level, and leads to the tripless operation during deceleration.

Please note that the actual deceleration time may be longer in this case.

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

DC bus AVR for decel.

P-gain

B055

VpnP

0000.2s

Proportional gain adjustment for

DC bus AVR function. Range is:

0.2 to 5.0

U

0.2

0.2

DC bus AVR for decel.

I-time

B056

VpnI

0000.2s

Integration time adjustment for

DC bus AVR function. Range is:

0.0 to 150.0

U

0.2

0.2

sec

DC bus AVR for decel.

D-time

B057

VpnD

0000.2s

Derivative time adjustment for

DC bus AVR function. Range is:

0.0 to 100.0

U

0.0

0.0

sec

DC bus AVR selection

B133

Vpn AVR

OFF

00

…Disabled

01

…Enabled

U

00

00

Threshold voltage of DC bus

AVR setting

B134

Vpn LVL

00380V

Setting of threshold voltage of

DC bus voltage to start DC bus

AVR function. Range is:
200V class

…330 to 395

400V class

…660 to 790

U

380

/760

380

/760

V

Threshold voltage to start DC bus AVR (B134)

DC bus AVR

t

t

DC bus voltage

Freq

Normal

operation

Confi

guri

ng Driv

e

Parameters