D” group: monitoring functions -6, D” group: monitoring functions – Hitachi X200 Series User Manual

Page 80

Advertising
background image

“D” Group: Monitoring Functions

You can access important parameter values with the “D” Group monitoring functions,

whether the inverter is in Run Mode or Stop Mode. After selecting the function code
number for the parameter you want to monitor, press the Function key once to show the

value on the display. In function D005 and D006, the intelligent terminal use individual

segments of the display to show ON/OFF status.

If the inverter display is set to monitor a parameter and powerdown occurs, the inverter

stores the present monitor function setting. For your convenience, the display

automatically returns to the previously monitored parameter upon the next powerup.

“D” Function

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

Units

Output frequency monitor

D001

FM

000.00Hz

Real time display of output

frequency to motor from
0.0 to 400.0Hz

Hz

Output current monitor

D002

Iout

0000.0A

Filtered display of output current to

motor (100 ms internal filter time

constant), range is
0 to 999.9 ampere

A

Rotation direction monitor

D003

Dir

STOP

Three different indications:
“F”

…Forward

“o”

…Stop

“r”

…Reverse

Process variable (PV),

PID feedback monitor

D004

FB

00000.00%

Displays the scaled PID process

variable (feedback) value (A075 is

scale factor),
0.00 to 99.99, 100.0 to 999.9

1000. to 9999., 1000 to 999,

and 10000 to 99900

% times

constant

Intelligent input

terminal status

D005

IN-TM

LHLHL

Displays the state of the intelligent

input terminals:

Intelligent output

terminal status

D006

OUT-TM

L H

Displays the state of the intelligent

input terminals:

ON

OFF

5 4

3

2

1

Terminal numbers

Terminal numbers

AL

11

ON

OFF

36

Confi

guri

ng Driv

e

Parameters