Overload Advance Notice Signal

When the output current exceeds a preset

value, the [OL] terminal signal turns ON.
The parameter C041 sets the overload

threshold. The overload detection circuit

operates during powered motor operation
and during regenerative braking. The

output circuits use open-collector

transistors, and are active low.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

when output current is more than the set
threshold for the overload signal

03

OL

Overload Advance
Notice Signal

OFF when output current is less than the set threshold

for the overload signal

Valid for inputs:

11, AL0 – AL2

Required settings

C041

Notes:
• The default value is 100%. To change the level

from the default, set C041 (overload level).

• The accuracy of this function is the same as the

function of the output current monitor on the

[FM] terminal (see

“Analog Output Operation”

on page 4–55

).

• The example circuit for terminal [11] drives a

relay coil. Note the use of a diode to prevent the

negativegoing turn-off spike generated by the

coil from damaging the inverter’s output
transistor.

Example for terminal [11] (default output
configuration shown – see

page 3-35

):

Example for terminal [AL0], [AL1], [AL2] (requires
output configuration – see

page 4-35 and 3-54

):

See I/O specs on

page 4-6

RY

Inverter output
terminal circuit

CM2

11

OL

AL1

Power
supply

Load

AL0

AL2

Inverter logic
circuit board

OL

t

Output

current

Threshold

Threshold

C041

C041

Power running

Regeneration

0

1

[OL]

signal

ON

ON

440

Operatio

ns and

Monitori

ng