A motor control system will obviously include a motor and inverter, as well as a breaker

or fuses for safety. If you are connecting a motor to the inverter on a test bench just to

get started, that’s all you may need for now. But a system can also have a variety of
additional components. Some can be for noise suppression, while others may enhance

the inverter’s braking performance. The figure and table below show a system with all

the optional components you may need in your finished application.

Name

Function

Breaker /
disconnect

A molded-case circuit breaker (MCCB), ground fault
interrupter (GFI), or a fused disconnect device. NOTE:

The installer must refer to the NEC and local codes to

ensure safety and compliance.

Input-side

AC Reactor

This is useful in suppressing harmonics induced on the

power supply lines and for improving the power factor.

WARNING: Some applications

must

use an input-side

AC Reactor to prevent inverter damage. See Warning on

next page.

Radio noise
filter

Electrical noise interference may occur on nearby
equipment such as a radio receiver. This magnetic choke

filter helps reduce radiated noise (can also be used on

output).

EMI filter (for

CE applications,
see

Appendix D

)

Reduces the conducted noise on the power supply wiring

between the inverter and the power distribution system.
Connect to the inverter primary (input) side.

EU version (with a suffix of -FEF have integrated EMC

Filter, which is category C1 for 200V class and C2 for
400V class.)

Radio noise

filter (use in
non-CE

applications)

This capacitive filter reduces radiated noise from the

main power wires in the inverter input side.

DC link choke

Suppress harmonics generated by the inverter.

However, it will not protect the input diode bridge

rectifier.

Radio noise

filter

Electrical noise interference may occur on nearby

equipment such as a radio receiver. This magnetic choke

filter helps reduce radiated noise (can also be used on
input).

Output-side
AC Reactor

This reactor reduces the vibration in the motor caused
by the inverter’s switching waveforms, by smoothing the

waveform to approximate commercial power quality. It

is also useful to reduce harmonics when wiring from the
inverter to the motor is more than 10m in length.

LCR filter

Sine wave shaping filter for output side.

NOTE: Note that some components are required for regulatory agency compliance (see
Chapter 5 and Appendix D).

Breaker,
MCCB or
GFI

From power supply

Motor

Thermal
switch

L1

L2

L3

T1

T2

T3

Inverter