Terminal Tightening Torque and Wire Size

The wire size range and tightening torque for field wiring terminals are presented in

the tables below.

Motor Output

Torque

Input

Voltage

kW

HP

Inverter Model

Power Terminal

Wiring Size

Range (AWG)

Ft-lbs

(N-m)

0.2

1/4

X200-002SFE/NFU

0.4

1/2

X200-004SFE/NFU

0.6

0.8

0.55

3/4

X200-005SFE

0.75

1

X200-007SFE/NFU

14

(75

°C only)

1.1

1 1/2

X200-011SFE

1.5

2

X200-015SFE/NFU

12

2.2

3

X200-022SFE/NFU

10

0.9

1.2

3.7

5

X200-037LFU

12

0.9

1.2

200V

Class

0.4

1/2

X200-004HFE/HFU

0.75

1

X200-007HFE/HFU

1.5

2

X200-015HFE/HFU

16

2.2

3

X200-022HFE/HFU

3.0

4

X200-030HFE

4.0

5

X200-040HFE/HFU

14

(60

°C only)

0.9

1.2

400V

Class

Torque

Terminal Connector

Wiring Size

Range (AWG)

Ft-lbs

(N-m)

Logic and Analog connectors

30 – 16

0.16 – 0.19

0.22 – 0.25

Relay connector

30 – 14

0.37 – 0.44

0.5 – 0.6

Wire Connectors

WARNING: Field wiring connections must be made by a UL Listed and CSA certified
ring lug terminal connector sized for the wire gauge being used. The connector must be
fixed using the crimping tool specified by the connector manufacturer.