Power Wiring Access – First, ensure no power

source of any kind is connected to the inverter.
If power has been connected, wait five

minutes after power down and verify the

Power LED is OFF to proceed. After removing
the front housing cover, the two housing

partitions that covers the power wiring exit

will be able to slide upward as shown to the
right. One at the upper side is for main power

input terminals, and the one at the lower side

is for the motor output side power terminals.

Notice the four wire exit slots in the housing

partition. This helps keep the wiring (to the

left) separate from signal-level logic or analog
wiring (to the right).

Remove the housing partitions and as shown

as set it aside in a secure place while wiring.
Never operate the inverter drive with the

partiti

on removed or the front housing

cover removed.

The power input wiring connect to the upper

terminals, and motor 3-phase wiring connect
to the lower row of the lower portion

terminals. The upper row of the lower part

terminals connect to optional braking units.

The following section in this chapter will

describe the system design and guide you

through a step-by-step installation process.
After the section on wiring, this chapter will

show how to use the front panel keys to access

functions and edit parameters.

26

Inverter Mountin

g

and i

n

st

all

a

tio

n

Inverter Mountin

g

and i

n

st

all
a

tio
n

Power input terminals

Motor connecting terminals
and terminals for other options
(DC link choke, Braking unit)