Force Operation from Digital Operator

This function permits a digital operator interface to override the following two settings

in the inverter:

A001 - Frequency source setting

A002 - Run command source setting

When using the [OPE] terminal input, typically A001 and A002 are configured for

sources other than the digital operator interface for the output frequency and Run

command sources, respectively. When the [OPE] input is ON, then user has immediate
command of the inverter, to start or stop the motor and to set the speed.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Forces the operator interface to override:

A001 - Frequency Source Setting, and A002 - Run

Command Source Setting

31

OPE

Force Operation

from Digital

Operator

OFF Parameters A001 and A002 are in effect again,

for the frequency source and the Run command

source, respectively

Valid for inputs:

C001~C005

Required settings

A001 (set not equal to 00)

A002 (set not equal to 02)

Notes:
• When changing the [OPE] state during Run

Mode (inverter is driving the motor), the
inverter will stop the motor before the new

[OPE] state takes effect.

• If the [OPE] input turns ON and the digital

operator gives a Run command while the
inverter is already running, the inverter stops

the motor. Then the digital operator can control

the motor.

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L

PCS P24

OPE

Operatio

ns and

Monitori

ng

429