List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

C144 Terminal [11] ON delay

R/W Range is 0.0 to 100.0 sec.

1153h 0 to 1000 0.1 sec

C145 Terminal [11] OFF delay R/W Range is 0.0 to 100.0 sec.

1154h 0 to 1000 0.1 sec

C148 Output relay ON delay

R/W Range is 0.0 to 100.0 sec.

1157h 0 to 1000 0.1 sec

C149 Output relay OFF delay

R/W Range is 0.0 to 100.0 sec.

1158h 0 to 1000 0.1 sec

Note 1:

Assume that the inverter current rating is 10000 (for C041).

The following table lists the holding registers for the “H” Group Motor Constants.

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

H003 Motor capacity

R/W

1165h

0 to 13

H203 Motor capacity, 2nd

motor

R/W

0…0.20kW

1…0.37kW
2…0.40kW

3…0.55 kW

4…0.75 kW
5…1.10 kW

6…1.50 kW

7…2.2 kW

8…3.0 kW
9…3.7 kW

10…4.0 kW

11…5.5 kW
12…7.5 kW

13…11.0kW

1541h

0 to 13

H004 Motor poles setting

R/W

1166h 2, 4, 6, 8 1 pole

H204 Motor poles setting, 2nd

motor

R/W

Four selections:

2 / 4 / 6 / 8

1542h 2, 4, 6, 8 1 pole

H006 Motor stabilization

constant

R/W

1168h 0 to 255

1

H206 Motor stabilization

constant, 2nd motor

R/W

Motor constant (factory set),

range is 0 to 255

1544h 0 to 255

1