B − 28 – Hitachi X200 Series User Manual

Page 255

Advertising
background image

List of Holding Registers

Network Data

Func.

Code

Name

R/W

Description

Reg.

Range

Res.

A071 PID enable

R/W Enables PID function,

two option codes:
00

…PID Disable

01

…PID Enable

1068h

0, 1

A072 PID proportional gain

R/W Proportional gain has a range of

0.2 to 5.0

1069h

2 to 50

0.1

A073 PID integral time

constant

R/W Integral time constant has a

range of 0.0 to 150 seconds

106Ah

0 to 1500

0.1 sec

A074 PID derivative time

constant

R/W Derivative time constant has a

range of 0.0 to 100 seconds

106Bh

0 to 1000

0.1 sec

A075 PV scale conversion

R/W Process Variable (PV), scale

factor (multiplier), range of 0.01

to 99.99

106Ch

1 to 9999

0.01

A076 PV source setting

R/W Selects source of Process

Variable (PV), option codes:
00

…[OI] terminal (current in)

01

…[O] terminal (voltage in)

02

…ModBus network

10

…Calculate function output

106Dh

0, 1, 2, 3

A077 Reverse PID action

R/W Two option codes:

00

…PID input = SP-PV

01

…PID input = -(SP-PV)

106Eh

0, 1

A078 PID output limit

R/W Sets the limit of PID output as

percent of full scale,
range is 0.0 to 100.0%

106Fh

0 to 1000

0.1 %

A081 AVR function select

R/W Automatic (output) voltage

regulation, selects from three

type of AVR functions, three

option codes:
00

…AVR enabled

01

…AVR disabled

02

…AVR enabled except during

deceleration

1070h

0, 1, 2

A082 AVR voltage select

R/W 200V class inverter settings:

00

…200

01

…215

02

…220

03

…230

04

…240

400V class inverter settings:
00

…380

01

…400

02

…415

03

…440

04

…460

05

…480

1071h

0 to 5

A085 Operation mode

selection

R/W Two option codes:

00

…Normal operation

01

…Energy-saver operation

1072h

0, 1

A086 Energy saving mode

tuning

R/W Range is 0.0 to 100 sec.

1073h

0 to 1000

0.1 %

B28

Appe

ndix B