Hitachi X200 Series User Manual

Page 71

Advertising
background image

Action

Display

Func./Parameter

(Starting point)

A003

Base frequency setting

Press the key and hold until Æ

A082

AVR voltage select

Press the key.

230

or

400

Default value for AVR voltage:

200V class = 230VAC

400V class = 400VAC (HFE)

= 460VAC (HFU)

Press the or key as needed.

215

Set to your motor specs (your display
may be different)

Press the key.

A082

Store parameter, returns to “A”
Group list

Set the Motor Current – The inverter has thermal overload protection that is designed

to protect the inverter and motor from overheating due to an excessive load. The

inverter’s uses the motor’s current rating to calculate the time-based heating effect.
This protection depends on using correct current rating for your motor. The level of

electronic thermal setting, parameter B012, is adjustable from 20% to 120% of the

inverter’s rated current. A proper configuration will also help prevent unnecessary
inverter trip events.

Read the motor’s current rating on its manufacturer’s nameplate. Then follow the steps

below to configure the inverter’s overload protection setting.

Action

Display

Func./Parameter

(Starting point)

A082

AVR voltage select

Press the key.

A- - -

“A” Group selected

Press the key.

b- - -

“B” Group selected

Press the key.

b001

First “B” Group parameter selected

Press the key and hold until Æ

b012

Level of electronic thermal setting

Press the key.

1.60

Default value will be 100% of

inverter rated current

Press the or key as needed.

1.80

Set to your motor specs (your display

may be different)

Press the key.

b012

Store parameter, returns to “B”

Group list

FUNC

STR

1

1

2

FUNC

1

FUNC

1

1

2

FUNC

STR

232

Inverter Mountin

g

and i

n

st

all

a

tio

n