Hitachi X200 Series User Manual

Page 113

Advertising
background image

“B” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

Selection of the non stop

operation

B050

IPS MODE

OFF

Two option codes:
00

…Disabled

01

…Enabled

U

00

00

Non stop operation start
voltage setting

B051

IPS V

0000.0V

Setting of DC bus voltage to start
non stop operation. Range is 0.0

to 1000.0

U

0.0

0.0

V

OV-LAD Stop level of non

stop operation setting

B052

IPS OV

0000.0V

Setting the OV-LAD stop level of

non stop operation. Range is 0.0
to 1000.0

U

0.0

0.0

V

Deceleration time of non stop

operation setting

B053

IPS DEC

0001.0s

Range is 0.01 to 3000

U

1.0

1.0

sec

Frequency width of quick

deceleration setting

B054

IPS F

0000.0Hz

Setting of the first quick

deceleration width. Range is 0.0

to 10.0

U

0.0

0.0

Hz

339