Analog input settings – Hitachi X200 Series User Manual

Page 87

Advertising
background image

Analog Input Settings

The inverter has the capability to accept an external analog input that can command

the output frequency to the motor. Voltage input (0-10 V) and current input (4-20mA)
are available on separate terminals ([O] and [OI] respectively). Terminal [L] serves as

signal ground for the two analog inputs. The analog input setting adjust the curve

characteristics between the analog input and the frequency output.

Please note that you cannot use the [O] and [OI] input at the same time.

Adjusting [O-L] characteristics – In the

graph to the right, A013 and A014 select the
active portion of the input voltage range.

Parameters A011 and A012 select the start

and end frequency of the converted output
frequency range, respectively. Together,

these four parameters define the major line

segment as shown. When the line does not
begin at the origin (A011 and A013 > 0),

then A015 defines whether the inverter

outputs 0Hz or the A011-specified frequency
when the analog input value is less than the

A013 setting. When the input voltage is

greater than the A014 ending value, the
inverter outputs the ending frequency

specified by A012.

Adjusting [OI-L] characteristics – In the
graph to the right, A103 and A104 select the

active portion of the input current range.

Parameters A101 and A102 select the start
and end frequency of the converted output

frequency range, respectively. Together,

these four parameters define the major line
segment as shown. When the line does not

begin at the origin (A101 and A103 > 0),

then A105 defines whether the inverter
outputs 0Hz or the A101-specified frequency

when the analog input value is less than the

A103 setting. When the input voltage is
greater than the A104 ending value, the

inverter outputs the ending frequency

specified by A102.

Adjusting integrated POT characteristics – Refer to the parameter A151~A155.

Max frequency

A012

A011

A014

100%

0V

10V

A013

0%

A015=00

A015=01

0

Input scale

%

Max frequency

A102

A101

A104

100%

0

20mA

A103

0%

A105=00

A105=01

0

Input scale

%

313

Confi

guri

ng Driv

e

Parameters