Pid on/off and pid clear – Hitachi X200 Series User Manual

Page 165

Advertising
background image

PID ON/OFF and PID Clear

The PID loop function is useful for controlling motor speed to achieve constant flow,

pressure, temperature, etc. in many process applications. The PID Disable function
temporarily suspends PID loop execution via an intelligent input terminal. It overrides

the parameter A071 (PID Enable) to stop PID execution and return to normal motor

frequency output characteristics. the use of PID Disable on an intelligent input terminal
is optional. Of course, any use of the PID loop control requires setting PID Enable

function A071=01.

The PID Clear function forces the PID loop integrator sum = 0. So, when you turn ON
an intelligent input configured as [PIDC], the integrator sum is reset to zero. This is

useful when switching from manual control to PID loop control and the motor is

stopped.

CAUTION: Be careful not to turn PID Clear ON and reset the integrator sum when the
inverter is in Run Mode (output to motor is ON). Otherwise, this could cause the motor

to decelerate rapidly, resulting in a trip.

Option

Code

Terminal

Symbol

Function Name

State

Description

ON

Disables PID loop execution

23

PID

PID Disable

OFF Allows PID loop execution

ON

Force the value of the integrator to zero

24

PIDC

PID Clear

OFF No change in PID loop execution

Valid for inputs:

C001~C005

Required settings

A071

Notes:

• The use of [PID] and [PIDC] terminals are

optional. Use A071=01 if you want PID loop

control enabled all the time.

• Do not enable/disable PID control while the

motor is running (inverter is in Run Mode).

• Do not turn ON the [PIDC] input while the

motor is running (inverter is in Run Mode).

Example (default input configuration shown—see

page 3–49

):

See I/O specs on

page 4–6.

5

4

3

2

1

L

PCS P24

PIDC PID

426

Operatio

ns and

Monitori

ng

Advertising