Non Stop Operation at Power OFF

Non stop operation at power OFF helps to avoid tripping or free-running of the motor

when power turns OFF during running. Inverter controls the internal DC bus voltage
by decelerating the motor, and finally makes the motor stop.

c

When the power turns OFF during running and the internal DC bus voltage of the

inverter comes down to the set level of B051, the inverter decreases the output
frequency, which is set in B054 in a short period. (In this moment the DC bus

voltage rises thanks to the regeneration and does not go down to the UV level.)

d

Continues deceleration according to the set value of B053. If the DC bus voltage

rises up to the set value of B052, the inverter stop deceleration to avoid OV tripping.

e

In this period the DC bus voltage decreases because of no power input.

f

When the DC bus voltage comes down to the set value of B051, the inverter starts

deceleration according to the set value of B053 again. After this will be the

repetition from d and finally comes to the motor to stop.

NOTE: If the DC bus voltage comes down to the UV level during this operation, the
inverter trips with undervoltage and motor will be free-run.

NOTE: If the set value of B052<B051, then the inverter changes internally the B052 to
B051. However the displayed value is not changed.

NOTE: This function cannot be interrupted until it is completed. So if the power is
recovered during this operation, wait until the operation is done (motor stops) and then
give the run command.

Power

DC bus voltage

Output frequency

b052
b051

Undervoltage
level

OFF

b054

b053

b053

b053

c

d

e

f

338

Confi

guri

ng Driv

e

Parameters