“B” Group: Fine Tuning Functions

The “B” Group of functions and parameters adjust some of the more subtle but useful

aspects of motor control and system configuration.

Automatic Restart Mode

The restart mode determines how the inverter will resume operation after a fault

causes a trip event. The four options provide advantages for your applications.

Frequency matching allows the inverter to read the motor speed by virtue of its residual
magnetic flux and restart the output at the corresponding frequency. The inverter can

attempt a restart a certain number of times depending on the particular trip event:

• Over-current trip, restart up to 3 times

• Over-voltage trip, restart up to 3 times

• Under-voltage trip, restarts up to 16 time

When the inverter reaches the maximum number of restarts (3 or 16), you must power

cycle the inverter to reset its operation.

Other parameters specify the allowable under-voltage level and the delay time before
restarting. The proper settings depend on the typical fault conditions for your

application, the necessity of restarting the process in unattended situations, and

whether restarting is always say.

If the actual power fail time is

shorter than the B002 set value,

inverter resumes from the set
frequency in B011.

The resuming mode is called

“frequency pull-in” and the
inverter performs reduced voltage

start to avoid overcurrent trip.

If the motor current exceeds the
B030 set value during this period,

inverter decelerates according to

the B029 set value and helps to
reduce the motor current.

And when the motor current is

less than the B030, inverter
increases the motor speed again.

The performance continues this

retry action until the motor speed
comes to the previous set speed.

Overload restriction (B021~B028) is not valid when frequency pull-in is activated.

If the actual power fail time is longer than the B002 set value, the inverter does not
resume and the motor will coast to stop.

332

Confi

guri

ng Driv

e

Parameters

<Example>

Power failure < allowable power fail

time(B022), Inverter resumes

Free-running

Input
power

Inverter
output

Motor
rotation

B003

B002

Allowable power

fail time

Retry wait time

Power fail

Motor
current

B030

Freq. Pull-in restart level

B029

Freq. Pull-in restart
Deceleration constant