DIP Switch Introduction

The inverter has internal DIP switches, located at the middle of the logic connectors as

shown below. This selection provides an introduction, and refers you to other chapter

that discuss the DIP switch in depth.

The 485/OPE (RS485/Operator) DIP switch configures the

inverter’s RS485 serial port. You can use either the inverter’s

integrated keypad or the OPE (OPE SR-mini) connected via a
cable to the serial port. In this case the SW7 should be set OPE

(default set). Inverter control via a ModBus network

communication requires the “485” setting. See “

Connecting the

Inverter to ModBus” on page B-3

for more details.

The SW8 is for the emergency signal input. If you turn this DIP

switch ON, the inverter is ready to receive emergency signal

from the dedicated terminal #3. Inverter shuts off the output by
means of pure hardware when a signal is given to the terminal.

It complies to EN954-1, category 3. Each signals related to this

emergency input must be in accordance with the norm.
Additionally, the logic input terminal assign will be changed

automatically if the SW8 is made ON. See

“Safe Stop” on page

4-32

for more details.