Additional Analog Input Settings

Input Range Settings – The parameters in the following table adjust the input

characteristics of the analog current input. When using the inputs to command the
inverter output frequency, these parameters adjust the starting and ending ranges for

the current, as well as the output frequency range. Related characteristic diagrams are
located in “

Analog Input Settings

” on page 3-13.

Analog sampling setting is the value specified in A016.

“A” Function

Defaults

Func.

Code

Name /

SRW Display

Description

Run

Mode

Edit

-FE

(EU)

-FU

(USA) Units

[OI]-[L] input active range

start frequency

A101

OI-EXS

0000.0Hz

The output frequency

corresponding to the analog input

range starting point,

range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

[OI]-[L] input active range

end frequency

A102

OI-EXE

0000.0Hz

The output frequency

corresponding to the current

input range ending point,
range is 0.0 to 400.0 Hz

U

0.0

0.0

Hz

[OI]-[L] input active range
start current

A103

OI-EX%S

00000%

The starting point (offset) for the
current input range,

range is 0. to 100.%

U

0.

0.

%

[OI]-[L] input active range

end voltage

A104

OI-EX%E

00000%

The ending point (offset) for the

current input range,
range is 0. to 100.%

U

100.

100.

%

[OI]-[L] input start frequency

enable

A105

OI-LVL

0Hz

Two options; select codes:
00

…Use offset (A101 value)

01

…Use 0Hz

U

01

01

Refer to parameter A011 to A015 for analog voltage input.

NOTE: You cannot give voltage input and current input ([O] and [OI] input) at the same
time on X200 series inverter.