Analog input operation -53, Analog input operation – Hitachi X200 Series User Manual

Page 192

Advertising
background image

Analog Input Operation

The X200 inverters provide for analog input to

command the inverter frequency output value.
The analog input terminal group includes the

[L], [OI], [O], and [H] terminals on the control

connector, which provide for Voltage [O] or
Current [OI] input. All analog input signals

must use the analog ground [L].

If you use either the voltage or current analog
input, you must select one of them using the

logic input terminal function [AT] analog type.

Refer to the table on next page showing the
activation of each analog input by combination

of A005 set parameter and [AT] terminal

condition. The [AT] terminal function is covered
in

“Analog Input Current/Voltage Select” on

page 4–22

. Remember that you must also set

A001 = 01 to select analog input as the
frequency source.

NOTE: If no logic input terminal is configured for the [AT] function, then inverter

recognizes that [AT]=OFF.

Using an external potentiometer is a common way

to control the inverter output frequency (and a good

way to learn how to use the analog inputs). The
potentiometer uses the built-in 10V reference [H]

and the analog ground [L] for excitation, and the

voltage input [O] for the signal. By default, the [AT]
terminal selects the voltage input when it is OFF.

Take care to use the proper resistance for the

potentiometer, which is 1~2 k

, 2 Watts.

Voltage Input – The voltage input circuit uses

terminals [L] and [O]. Attach the signal cable’s

shield wire only to terminal [L] on the inverter.
Maintain the voltage within specifications (do not

apply negative voltage).

Current Input – The current input circuit uses
terminals [OI] and [L]. The current comes from a

sourcing

type transmitter; a

sinking

type will not

work! This means the current must flow into
terminal [OI], and terminal [L] is the return back

to the transmitter. The input impedance from

[OI] to [L] is 250 Ohms. Attach the cable shield
wire only to terminal [L] on the inverter.

AM H

O OI

L

+V Ref.

Voltage input

Current input

A GND

AM H

O OI

L

Freq.
setting

A001

V/I input
select

[AT]

Å

+ -

4-20 mA

0-10 V

AM H

O OI

L

1 to 2k

Ω, 2W

0 to 9.6 VDC,
0 to 10V nominal

AM H

O OI

L

+ -

4 to 19.6 mA DC,
4 to 20mA nominal

AM H

O OI

L

Å

See I/O specs on

page 4-6

.

453

Inverter Mountin

g

and i

n

st

all
a

tion