Hitachi X200 Series User Manual

Page 127

Advertising
background image

Input Function Summary Table

Option

Code

Terminal

Symbol

Function Name

Description

ON

Adds the A145 (add frequency) value to the output

frequency

50

ADD

ADD frequency

enable

OFF Does not add the A145 value to the output frequency
ON

Force inverter to use input terminals for output

frequency and Run command sources

51

F-TM

Force Terminal

Mode

OFF Source of output frequency set by A001 and source of

Run command set by A002 is used

ON

To charge up the internal boot-strap capacitor so to

start motor immediately after the RUN command is

given.

52

RDY *

Inverter Ready

OFF Inverter operates normal.
ON

The inverter uses 2nd motor parameters for generating
frequency output to motor. The selection of 1st or 2nd

motor is available during Stop Mode or Run Mode.

53

SP-SET

Special set

OFF The inverter uses 1st (main) motor parameters for

generating frequency output to motor.

ON

Inverter recognizes that the emergency signal is given,

and shuts off the output.

Use together with EXT input when the system
including the inverter must comply to EN954-1.

Refer to “Safe Stop” on page 4-32.

64

EMR *

Safe Stop

OFF Inverter operates normal
ON

(input ignored)

255

-

(No function)

OFF (input ignored)

NOTE: When using the Multi-speed Select settings CF1 to CF4, do not display
parameter F001 or change the value of F001 while the inverter is in Run Mode (motor

running). If it is necessary to check the value of F001 during Run Mode, lease monitor
D001 instead of F001.

HIGH VOLTAGE: When set RDY function ON, there will be a voltage appears at motor
output terminals U, V and W even if the motor is in stop mode. So never touch the

inverter power terminals even the motor is not running.

NOTE: The EMR is not programmable, but will be assigned automatically when the
hardware switch S8 is made ON. When the EMR is assigned, function assignments of
terminal 3, 4 and 5 are automatically changed as follows. Please also refer to Safety

Stop paragraph.

Safety Stop switch condition

Terminal

Number

Default setting

Safe Stop switch

S8 = OFF

Safety Stop switch

S8 =

ON

Safety Stop switch

S8 =

ON Æ OFF

1

FW

FW

FW

2

RV

RV

RV

3

CF1

EMR

[HW based for 1b input]

- (No func.)

4

CF2 [US ver. :USP]

RS

[HW based for 1a input]

RS

[Normal 1a]

5

RS

(PTC assignable)

- (No func.)

- (No func.)

353

Config

uri

ng Driv

e

Parameters