Chapter 4 Communication

In addition to the selectable protocols listed above, the Ethernet port
supports Modbus TCP beginning with Master Module firmware
version 4 and Ethernet firmware version 3.

Refer to the description of the Modbus RTU protocol beginning on

page 92

for further information.

The Ethernet port supports up to 64 concurrent connections.

The power monitor supports the following network requests.

Protocol Selection Table

Protocol

RSLinx
Connection Type

Pure CSP Client
Compatibility(1)

RSEnergyMetrix
and RSPower
Compatibility

Logix and
MicroLogix
Compatibility

Implicit
Messaging
Compatibility

CIP (default)

EtherNet/IP

No

Yes

Yes

Yes

CSP

DF1 (CSP)

Yes

No

No

No

CIP/CSP

DF1 (CSP)

Yes

No

Yes

Yes

Ethernet Message Types

Message type

CIP PLC-5 Typed Write

CIP PLC-5 Typed Read

CIP Generic Assembly Object (class 04), Get & Set Attribute Single for Attribute 3 (data)

CIP Generic Assembly Object (class 04), Get Attribute Single for Attribute 3 (size)

CIP SLC 500 Typed Write

CIP SLC 500 Typed Read

CIP Data Table Read (using CSP/PCCC addressing for example F15:0)

CIP Data Table Write

CSP / PCCC PLC-5 Typed Write

CSP / PCCC PLC-5 Typed Read

CSP / PCCC Protected Typed Logical Read, 2 address fields

CSP / PCCC Protected Typed Logical Read, 3 address fields

CSP / PCCC Protected Typed Logical Write, 2 address fields

CSP / PCCC Protected Typed Logical Write, 3 address fields

CSP / PCCC Word Range Read

CSP / PCCC Word Range Write

CSP / PCCC Diagnostic Loopback