List of setpoint types parameters, List of setpoint types – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 216

Advertising
background image

216

Publication 1404-UM001F-EN-P - November 2009

Appendix A Powermonitor 3000 Data Tables

13

40714

Accumulated time
Integer

0…9999

Seconds

-

14

40415

Accumulated time
Exponent

-1…21

-

-

15

40716

Clear time
accumulator
command

0…1

-

0

(1)

On the M6 and M8, setpoint #19 and #20 default to detect voltage sag and voltage swell. See Sag and Swell,

page 174

.

Setpoint Setup/Read-back Select and Status

Element
No.

Modbus
Address

Element name

Range

Units

Default
Value

Comment

List of Setpoint Types Parameters

Applies to

Setpoint Setup/Read-back Select and Status Parameters on

page 215

.

PM3000 Type

See table

List of Setpoint Types

Param.
No.

Parameter Name

M4
M5

M
6

M
8

Comment

0

Not used

• •

Disables the setpoint

1

Voltage

(1)

• •

Refer to Metering Voltage, Current, and Frequency Result Parameters

2

Current

(1)

• •

3

Voltage unbalance

• •

Refer to Metering Sequence Voltage, and Current Results Parameters

4

Current unbalance

• •

5

Neutral current

• •

6

W

• •

Refer to Metering Power Results Parameters

7

VAR

• •

8

VA

• •

9

Total true PF

• •

Refer to Metering Power Factor Results Parameters

10

Total disp PF

• •

11

Total dist PF

• •

12

W demand

• •

Refer to Metering Demand Results Parameters

13

VAR demand

• •

14

VA demand

• •

15

Amp demand

• •

16

Projected amp demand

• •

17

Projected W Demand

• •

18

Projected VAR Demand

• •

19

Projected VA Demand

• •

20

Frequency

• •

Refer to Metering Voltage, Current, and Frequency Result Parameters

21

Phase rotation

• •

Refer to Metering Sequence Voltage, and Current Results Parameters