Appendix A Powermonitor 3000 Data Tables

Event Log Configuration/Read-back Record Select Parameters

CSP File No.

N28

Remote I/O BT

9

CIP Assy. Inst.

32 (Write), 33 (Read)

No. of Elements

6

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Applies to:

Event Log Results Parameters on

page 229

Event Log Configuration/Read-back Record Select

Element
No.

Modbus
Address

Element Name

Range

Default
Value

Comment

0

41001

Password

0…9999

0

Required for configuration, -1 for readback
select, returns -1

1

41002

DeviceNet unique write identifier

-32,768…32,767

0

Refer to DeviceNet Unique Write Identifier on
page 103

2

41003

Read-back mode

0…6

2

Refer to Configuring the Event Log by Using
Communication on page 146

3

41004

Enable/disable logging status
input changes

0…1

0

4

41005

# events in the event log

1…50 (M4,M5)
1…100 (M6, M8)

-

5

41006

Enable/disable logging of
time/date set

0…1

1