Powermonitor 3000 Data Tables Appendix A

14

30615

ASIC build #

0…9999

Revision number of the code that was used to fabricate the
ASIC.

15

30616

Option communication FRN

0…9999

100 indicates version 1.00, 103 indicates version 1.03… 0 =
none (catalog numbers ending in -000, -232)

16

30617

Display module FRN

0…9999

104 indicates version 1.04, 105 indicates version 1.05…
Returns 0 if no DM connected

17

30618

Reserved 0

Returns

0

18

30619

Digital board revision

0…7

0 = 02A, 1 = 03A…

19

30620

Analog board revision

0…7

0 = 02A, 1 = 03A…

20

30621

Reserved

0

Returns 0

21

30622

Reserved 0

Returns

0

22

30623

MM Device ID

0…255

Sequentially assigned at time of manufacture. May not be
changed.

23

30624

Master module type, current

4,5,6,or 8

4 = M4, 5 = M5, 6 = M6, 8 = M8; reflects any upgrades

24

30625

Display module type

0…1

0 = No display module connected
1 = 1404-DM connected to master module

25

30626

Option communication type

-

00 = No optional communication (native RS-485 only)
81 = DeviceNet version 1
82 = ControlNet
84 = Remote I/O
86 = RS-232
88 = DeviceNet version 2
89 = IEC870 comm card

26

30627

Accuracy Class

0…2

Indicates revenue metering accuracy class as manufactured
(refer to

page 29

).

0 = Class 1
1 = Class 0.5
2 = Class 0.2

Selftest/Diagnostic Results

Element
No.

Modbus
Address

Element name

Range

Comment

TIP

This is not truly a data table, but a reply to a PCCC diagnostic status
request (used by RSWho to display text and an icon for the
Powermonitor 3000 unit). This data is not accessible using Modbus.

DF1 PCCC Diagnostic Status Reply Parameters

Byte

Bits

Contents

Description

1

0…1

Mode/status

Unused

2…3

4…7

2

0…7

Type extender

EE

3

0…7

Extended interface type

36h = DF1 half-duplex slave (via native RS485 port or RS-232 port)
65h = Ethernet

4

0…7

Extended processor type

8Ah; 1404 Powermonitor 3000 products