Status error codes, Configuring the event log by using communication – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 146

Advertising
background image

146

Publication 1404-UM001F-EN-P - November 2009

Chapter 7 Data Logging

Configuring the Event Log by Using Communication

You may configure the Event Log by performing a valid table write to
the

Event Log Configuration/Read-back Record Select

table. This

read/write data table contains these six integer elements:

Password: A valid password is required to set configuration
options or -1 to select a record for read-back

DeviceNet unique write identifier

Read-back mode: see below

Status input logging: 0 disables; 1 enables

Number of events logged: this read-only element is ignored on a
write

Time/date set logging: 0 disables; 1 enables

Status Error Codes

Bits Hex

Description

bit 0

0001h

Master module code flash status

bit 1

0002h

Master module data flash status

bit 2

0004h

Master module RAM Status

bit 3

0008h

Reserved for factory use

bit 4

0010h

Master module NVRAM status

bit 5

0020h

Master module data acquisition status

bit 6

0040h

Master module real time clock status

bit 7

0080h

Reserved for factory use

bit 8

0100h

Reserved for factory use

bit 9

0200h

Display module status

bit 10

0400h

Master module watchdog timer status

bit 11

0800h

Master module optional communication status

bit 12

15

1000h
-8000h

Reserved for factory use