Chapter 4 Communication

The RS-232 communication standard supports point-to-point
communication between TWO stations or nodes, with a maximum
cable length of 15.24 m (50.0 ft). You may not use the optional RS-232
port and the native RS-485 port at the same time.

Optional RS-232 Communication Configuration Summary

Parameter Description

Range

Default User

Setting

Port

Select active serial port

RS-232
RS-485

RS-232

Protocol DF1

Full-duplex

DF1 Half-duplex
Slave
Modbus RTU
Slave
Auto-Sense

Auto-Sense

Delay

Time between receiving a
request and transmitting
a response

0…75 ms

10 ms

Communication
Rate

RS-485 port
communication bit rate

1.2 Kbps
2.4 Kbps
4.8 Kbps
9.6 Kbps
19.2 Kbps
38.4 Kbps
57.6 Kbps

9600 baud

Node Address

Uniquely identifies the
Powermonitor device on
a multi-drop network

1…247 Unit

ID

number

Data Format

Data bits / Stop bits /
Parity

8 / 1/ none
8 / 1/ even
8 / 1/ odd

8 / 1 / none

Flow Control
(Handshaking)

RS-232 hardware flow
control

0 - none
1 - RTS/CTS

0 - none

Inter-Character
Timeout

Mimimum delay between
characters that indicates
end of Modbus message
packet

0 to 6553 ms

0 (= 3.5
character
times)

Error Checking

BCC, CRC

CRC