Publication 1404-UM001F-EN-P - November 2009

59

Powermonitor 3000 Unit Operations Chapter 3

DST is disabled by default. When enabled, the default start time is
2:00 a.m. on the second Sunday in March, and the default end time is
2:00 a.m. on the first Sunday in November. This corresponds to US
Daylight Saving Time beginning in 2007.

Daylight Saving Time Configuration Summary

Parameter Name

Range

Default

User Setting

DST Enable

0

1

0

DST Start Month

1

12

3

DST Start Day

0

6

0

DST Start Day Instance

1

5

2

DST Start Hour

0

23

2

DST End Month

1

12

11

DST End Day

0

6

0

DST End Day Instance

1

5

1

DST End Hour

0

23

2