Powermonitor 3000 Unit Operations Chapter 3

sends out a demand sync broadcast when configured as a
Master (Ethernet units).

starts the projected demand calculations from the beginning
again.

Entering a value of 0 disables this function.

For more information about this feature read the section Network
Demand / Time Configuration
on

page 55

.

Projected Demand Type specifies the type of calculation used for
projected demand. Selections include the following:

Instantaneous (default)

First-order

Second-order

Relay and KYZ Pulse Operation Setup

Use these configuration parameters to select how the relay and KYZ
solid-state outputs are controlled. Relay control source controls the
selection which includes the following:

Disabled

Wh forward

Wh reverse

VARh forward

VARh reverse

Vah

Ah

Setpoints (default)

Remote I/O or DeviceNet discrete control

The Pulse output scale factor sets the number of measurement
increments per pulse. Range 1…30,000, default 10. The Pulse output
width parameter determines the pulse width in milliseconds.
Range 40…2000 or 0 to transition the output KYZ-style. Default is 0.