Appendix A Powermonitor 3000 Data Tables

Basic Device Configuration Parameters

CSP File No.

F10

Remote I/O BT

20

CIP Assy. Inst.

4 (Write), 5 (Read)

No. of Elements

8 (M4, M5), 9 (M6, M8)

User Configurable No

Data Type

Floating point

Data Access

Read / Write

PM3000 Type

See table

Basic Device Configuration

Element
No.

Modbus
Address

Element name

M4
M5

M
6

M
8

Range

Units

Defaul
t
Value

Comment

0

40001-2

Password

• •

0…9999

-

0

Valid password required to change
configuration. Returns -1

1

40003-4

Wiring mode

• •

0…8

-

6

0 = Delta 3 CT
1 = Delta 2 CT
2 = Direct Delta 3 CT
3 = Direct Delta 2 CT
4 = Open Delta 3 CT
5 = Open Delta 2 CT
6 = Wye
7 = Single Phase
8 = Demo

2

40005-6

Potential transformer (PT)
primary

• •

1.0…
10,000,000.0

Volts

480.0

The high side of the PT ratio (xxx:xxx)

3

40007-8

PT secondary

• •

1.0…600.0

Volts

480.0

The low side of the PT ratio (xxx:xxx)

4

40009-10

I1/I2/I3 current
transformer (CT) Primary

• •

1.0…
10,000,000.0

Amps

5.0

The high side of the CT ratio
(xxx:xxx)

5

40011-12

I1/I2/I3 CT secondary

• •

1.0…5.0

Amps

5.0

The low side of the CT ratio (xxx:xxx)

6

40013-14

I4 CT primary

• •

1.0…
10,000,000.0

Amps

5.0

The high side of the I4 CT ratio
(xxx:xxx)

7

40015-16

I4 CT secondary

• •

1.0…5.0

Amps

5.0

The low side of the I4 CT ratio
(xxx:xxx)

8

40017-18

Nominal system voltage

• •

1.0…
10,000,000.0

Volts

480.0

Value is used in the default Sag and
Swell setpoints. (M6 and M8 only)
Nominal line-to-line voltage for Delta
mode and line-to-neutral for Wye and
single-phase modes