Remote i/o – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual
Page 201
Advertising
Publication 1404-UM001F-EN-P - November 2009
201
Powermonitor 3000 Data Tables Appendix A
Remote I/O
Element
No.
Modbus
Address
Element name
Range
Default
Value
Comment
0
40401
Password
0…9999
0
Valid password required to change configuration data. Returns -1
1
40402
Logical rack address
1…63
1
The scanner uses rack address 0
2
40403
Module group
0,2,4,6
0
0 = Group 0 (acts like the first 2 rack slots)
2 = Group 2
4 = Group 4
6 = Group 6
3
40404
Last rack
0…1
0
0 = No
1 = Yes
4
40405
Baud rate
0…2
0
0 = 57.6 Kbps
1 = 115.2 Kbps
2 = 230.4 Kbps
5
40406
Reserved
0
0
Reserved. Must be 0 on a write, returns 0
6
40407
7
40408
8
40409
9
40410
10
40411
11
40412
12
40413
13
40414
14
40415
15
40416
16
40417
17
40418
18
40419
19
40420