Powermonitor 3000 Data Tables Appendix A

Metering Power Factor Results Parameters

CSP File No.

F19

Remote I/O BT

33

CIP Assy. Inst.

18

No. of Elements

13

User Configurable No

Data Type

Floating point

Data Access

Read only

PM3000 Type

All

Metering Power Factor Results

Element
No.

Modbus
Address

Element name

Units

Range

Comment

0

30501-02 L1 True Power Factor

Percent

-100…100

Ratio between power and apparent power.
+ = Lead
- = Lag

1

30503-04 L2 True Power Factor

-100…100

2

30505-06 L3 True Power Factor

-100…100

3

30507-08 Three-phase True PF

-100…100

4

30509-10 L1 Displacement Power Factor

-100…100

Cosine of the phase angle between the fundamental
voltage and current.
+ = Lead
- = Lag

5

30511-12 L2 Displacement Power Factor

-100…100

6

30513-14 L3 Displacement Power Factor

-100…100

7

30515-16 Three-phase Displacement PF

-100…100

8

30517-18 L1 Distortion Power Factor

0…100

The ratio between the magnitude of the fundamental
and the sum of the magnitudes for all of the current
harmonics.

9

30519-20 L2 Distortion Power Factor

0…100

10

30521-22 L3 Distortion Power Factor

0…100

11

30523-24 Three-phase Distortion PF

0…100

12

30525-26 Metering iteration

-

0…32,767

Increments by 1…32,767, rolls over to 0.