Chapter 4 Communication

Set EtherNet/IP I/O Connection

Ethernet Powermonitor 3000 units support a Class 1 connection to
Instance 1 and 2.

1. To utilize this scheduled connection to a ControlLogix controller,

open the controller program offline in RSLogix 5000 software.

2. Select the 1756-ENET/B or 1756-ENBT/A module in the I/O

configuration.

3. Add the power monitor as a Generic Ethernet Module.

I/O Connection Setup

shows a typical configuration.

I/O Connection Setup

4. Select Data – INT as the Communication Format.

5. Enter the IP address of the power monitor.

6. Set the Connection Parameters as shown for the default

configuration.

If you change the configuration of the input assembly instance,
enter its new size in Instance 1 here.

TIP

If you wish to establish a Class 1 connection with more than one
controller to the same power monitor, use instance 1 and 2 for the
first controller and use instance 1 and 255 for all remaining controllers
(instance 255 is a placeholder instance since instance 2 only supports
one connection). If the controller loses its connection to instance 1
and 2, the instance 255 connection is also lost.