Powermonitor 3000 Data Tables Appendix A

Remote I/O, DeviceNet, EtherNet/IP and ControlNet I/O Messaging Parameters

CSP File No.

N/A

Remote I/O BT

N/A

CIP Assy. Inst.

1 (Read), 2 (Write)

No. of Elements

2 (Default)

User Configurable Yes (DeviceNet, EtherNet/IP and ControlNet)

Data Type

Integer (Selectable as Floating Point with DeviceNet, EtherNet/IP and ControlNet)

Data Access

Read/Write

PM3000 Type

All

Remote I/O Discrete Data Provided by Powermonitor (Remote I/O Input Data)

Element
No.

Element name

Range

Comment

1

Relay, KYZ, and alarm bits

-

Bit

Description

00…07

Reserved, used internally for BT information

08

Form C relay state (setpoint output flag 1)
0 = De-energized and not forced
1 = Energized and not forced

09

KYZ output state (setpoint output flag 2)
0 = De-energized and not forced
1 = Energized and not forced

10

Setpoint output flag 3 state

11

Setpoint output flag 4 state

12

Setpoint output flag 5 state

13

Setpoint output flag 6 state

14

Setpoint output flag 7 state

15

Setpoint output flag 8 state

2

Status input bits

Bit

Description

00

Status input 1 state

01

Status input 2 state

02…05

Reserved, returns 0

06

New oscillograph (M6, M8 only)
Indicates at least one capture has been triggered, saved, and is
ready to be read. This bit is cleared when all captures are cleared.

07…11

Reserved, returns 0

12…14

Reserved, used internally for BT information

15

Reserved, returns 0