Publication 1404-UM001F-EN-P - November 2009

Chapter 8 Advanced Features

Transient Capture

Transient Analysis Configuration

Perform a table write to the

Transient Analysis

Configuration/Read-back Select

to configure transient analysis. This

read/write table of 13 floating-point elements contains the following
configuration, command and read-back select parameters:

Password: required for configuration and command. Use a valid
password or -1 for read-back select. Range 0000…9999,
default 0, returns -1

DeviceNet unique write identifier: range -32,768…32,767,
default 0

Capture number: selects a capture for read-back. Range 0…6,
default 1

Cycle number: selects a cycle for read-back. Range 1…12,
default 1

Read-back mode: 0 = Auto-increment mode; cycle number
increments after each read of the

Transient Analysis Metering

Results

table. 1 = Manual-increment mode; only mode supported

by DeviceNet and Ethernet communication. Default 0

Detection mode: selects channels to monitor. 0 disables transient
detection, 1 = voltage channels only, 2 = current channels.
Default 1

Auto-threshold set command: 0 = do nothing, 1 = set threshold.
Default 0

Auto-threshold set duration: range: 1…3600 seconds, default 10