Transient analysis configuration/read-back select, Transient analysis, Configuration/read-back select – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 249: Transient, Analysis configuration/read-back select, Table

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

249

Powermonitor 3000 Data Tables Appendix A

Transient Analysis Configuration/Read-back Select Parameters

CSP File No.

F43

Remote I/O BT

44

CIP Assy. Inst.

52 (Write), 53 (Read)

No. of Elements

10

User Configurable No

Data Type

Floating Point

Data Access

Read / Write

PM3000 Type

M8 only

Applies to

Transient analysis metering results

Transient Analysis Configuration/Read-back Select

Element
No.

Modbus
Address

Element Name

Range

Default
Value

Comment

0

-

Password

0…9999

0

Required for configuration, -1 for readback select,
returns -1.

1

-

DeviceNet unique write
identifier

-32,768…32,767

0

Refer to DeviceNet Unique Write Identifier on
page 103

.

2

-

Capture #

0…6

1

Refer to Transient Analysis Configuration on
page 180

.

3

-

Cycle #

1…12

1

4

-

Read-back mode

0…1

0

5

-

Detection mode

0…3

1

6

-

Reserved

0

0

7

-

Auto-threshold set command

0…1

0

8

-

Auto-threshold set duration

1…3600

10

9

-

Auto-threshold set margin

1.0…100.0

20.0

10

-

Voltage trigger threshold

0.1…100.0

10.0

11

-

Current trigger threshold

0.1…100.0

10.0

12

-

Auto-threshold duration time
left

0

0