230

Publication 1404-UM001F-EN-P - November 2009

Appendix A Powermonitor 3000 Data Tables

Status Error Codes

Bits Hex

Description

bit 0

0001h

Master module code flash status

bit 1

0002h

Master module data flash status

bit 2

0004h

Master module RAM Status

bit 3

0008h

Reserved for factory use

bit 4

0010h

Master module NVRAM status

bit 5

0020h

Master module data acquisition status

bit 6

0040h

Master module real time clock status

bit 7

0080h

Reserved for factory use

bit 8

0100h

Reserved for factory use

bit 9

0200h

Display module status

bit 10

0400h

Master module watchdog timer status

bit 11

0800h

Master module optional communication status

bit 12…15

1000h…8000h

Reserved for factory use