Publication 1404-UM001F-EN-P - November 2009

237

Powermonitor 3000 Data Tables Appendix A

Harmonic Analysis Configuration/Read-back Select Parameters

CSP File No.

N33

Remote I/O BT

14

CIP Assy. Inst.

39 (Write), 40 (Read)

No. of Elements

9

User Configurable No

Data Type

Integer

Data Access

Read /Write

PM3000 Type

See table

Applies to:

Harmonic Results; THD, Crest Factor, and More Parameters on

page 238

(All models)

Harmonic Results; Odd Harmonics 1…21 Parameters on

page 239

,Harmonic Results;

Odd Harmonics 23…41 Parameters on

page 240

, Harmonic Results; Even Harmonics

2…20 Parameters on

page 241

, Harmonic Results; Even Harmonics 22…40

Parameters on

page 242

(M6 & M8)

Harmonic Results; Odd Harmonics 43…63 Parameters on

page 256

, Harmonic Results;

Even Harmonics 42…62 Parameters on

page 257

(M8 only)

Harmonic Analysis Configuration/Read-back Select

Element
No.

Modbus
Address

M4
M5

M
6

M
8

Element Name

Range

Default
Value

Comment

0

41201

• •

Password

0…9999

0

Required for configuration, -1 for readback
select, returns -1.

1

41202

• •

Channel

1…9

1

Refer to Configuring Harmonic Analysis on
page 171

.

2

41203

• •

Read-back mode

0…1

0

3

41204

Reserved

0

0

• •

Individual harmonic data type

0…1

0

4

41205

Reserved

0

0

• •

Enable/disable Harmonics

0…1

1

5

41206

Reserved

0

0

• •

IEEE-519 Max I

sc

Integer

0…9999

0

6

41207

Reserved

0

0

• •

IEEE-519 Max I

sc

Exponent

-4…21

0

7

41208

Reserved

0

0

• •

IEEE 519 Max I

dmnd

Integer

0…9999

0

8

41209

Reserved

0

0

• •

IEEE 519 Max I

dmnd

Exponent

-4…21

0