Min/max log results parameters, Min/max log results, Min/max log results parameters on – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 227

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

227

Powermonitor 3000 Data Tables Appendix A

Min/Max Log Results Parameters

CSP File No.

F27

Remote I/O BT

28

CIP Assy. Inst.

31

No. of Elements

11

User Configurable No

Data Type

Floating Point

Data Access

Read only

PM3000 Type

All

Min/Max Log Results

Element
No.

Modbus
Address

Element Name

Range

Comment

0

30801-02

Parameter # being returned

1…73

Refer to Reading Data from the Trend Log on page 152

1

30803-04

MIN value for parameter

-999.9x10

21

…999.9x10

21

2

30805-06

MAX value for parameter

-999.9x10

21

…999.9x10

21

3

30807-08

MIN timestamp;

year

month/day

hour/minute

sec/hsec

1998…2097

4

30809-10

0101…1231

5

30811-12

0000…2359

6

30813-14

0000 …5999

7

30815-16

MAX timestamp;

year

month/day

hour/minute

sec/hsec

1998…2097

8

30817-18

0101…1231

9

30819-20

0000…2359

10

30821-22

0000…5999