Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 192

Advertising
background image

192

Publication 1404-UM001F-EN-P - November 2009

Appendix A Powermonitor 3000 Data Tables

TIP

Data appears in the first two words of the input image table
corresponding to the Powermonitor 3000 logical rack. For example,
with the unit configured as Rack 1, Group 1 in a 1747-SN scanner
residing in Slot 2, the data will appear in words I:2.8 and I:2.9 of the
data table.

Remote I/O Discrete Data Accepted by Powermonitor Units (Master Output Data)

Element
No.

Element name

Range

Comment

1

Relay control

0 or 128

0 (Bit 8 = 0): De-energize
128 (Bit 8 = 1): Energize
Must be enabled by Control source parameter

2

KYZ control

DeviceNet, EtherNet/IP, and ControlNet I/O Data Provided by Powermonitor Units (Scanner Input Data; Instance 1)

Element
No.

Element name

Range

Comment

0

Relay output status

0…3

0 = De-energized & not forced
1 = Energized & not forced
2 = Forced de-energized
3 = Forced energized

1

Solid-state KYZ output status

2

Alarm output word

0…FFFF

Bitfield indicates state of 16 alarm output flags; 0 = released, 1 = asserted
Bit 0 = relay/setpoint output flag 1
Bit 1 = KYZ/setpoint output flag 2
Bit 2 = setpoint output flag 3

Bit 15 = setpoint output flag 16

3

Status inputs state

0…7

Bit 0 = status input 1; 0 = open, 1 = contact closure detected
Bit 1 = status input 2; 0 = open, 1 = contact closure detected
Bit 2 = demand sync timeout; 1 = the demand delay expired before the next
expected external demand sync. This bit clears when the next external
demand sync occurs.

Refer to Advanced Device Configuration Parameters

element 23.
Bits 3…15 = unused (always 0)

4

Status input #1 counter

0…
29,999

Counts to 29,999, rolls over to 0.

5

Status input #2 counter

TIP

Size and content of Instance 1 may vary depending on user
configuration.

Refer to User-configured Data Table on page 121

for

more information.

DeviceNet, EtherNet/IP, and ControlNet I/O Data Accepted by Powermonitor Units (Scanner Output Data; Instance 2)

Element
No.

Element name

Range

Default

Value

Comment

0

Relay output

0…1

-

0 (Bit 8 = 0): De-energize
256 (Bit 8 = 1): Energize
Must be enabled by Control source parameter

1

Solid-state KYZ output

0…1