Date and time parameters, Date and time – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 195

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

195

Powermonitor 3000 Data Tables Appendix A

Date and Time Parameters

CSP File No.

N11

Remote I/O BT

12

CIP Assy. Inst.

6 (Write), 7 (Read)

No. of Elements

8

User Configurable No

Data Type

Integer

Data Access

Read / Write

PM3000 Type

All

Date and Time

Element
No.

Modbus
Address

Element name

Range

Default
Value

(2)

Comment

0

40101

Password

0…9999

0

Valid password required to change the date and time.
Returns -1

1

40102

Date: year

1998…
2097

1998

1 = January, 2 = February,…12 = December
The internal clock adjusts the date for leap year.

2

40103

Date: month

1…12

1

3

40104

Date: day

1…31

(1)

1

4

40105

Time: hour

0…23

0

0 = 12am, 1 = 1am,…23 = 11pm
The internal clock does not adjust for daylight saving time.

5

40106

Time: minute

0…59

0

6

40107

Time: seconds

0…59

0

7

40108

Time: hundredths of seconds

0…99

0

(1)

On a write, the maximum value for day depends on the values written to month and the year.

(2)

The data and time default values are set if one of the following three conditions occur:
- When the device is first powered-up at the factory.
- A device power-up following the depletion of the real-time clock power source.
- In the event of an abnormal condition which may cause the real-time clock to contain values which are not in the valid range.
The date and time are not set to the default values when Restore Factory Defaults is performed via the display module or communication port.