Rs-232 – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 203

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

203

Powermonitor 3000 Data Tables Appendix A

RS-232

Element
No.

Modbus
Address

Element name

Range

Default
Value

Comment

0

40401

Password

0…9999

0

Required to change configuration data. Returns -1

1

40402

Hardware port

0…1

0

Select active port
0 = RS-232 port
1 = Native RS-485 port

2

40403

Protocol

0…3

0

Communication protocol for the native
communication port.
0 = DF1 half-duplex slave
1 = Modbus RTU slave
2 = Auto Sense - Selects the protocol based on the
incoming communication packets
3 = DF1 full-duplex

3

40404

Delay

0…15

2 (10 ms)

Specifies the delay before responding to an
external request., useful with slow external
devices (such as RF modems)

4

40405

Baud rate

0… 6

3

0 = 1.2 Kbps
1 = 2.4 Kbps
2 = 4.8 Kbps
3 = 9.6 Kbps
4 = 19.2 Kbps
5 = 38.4 Kbps
6 = 57.6 Kbps

5

40406

RS-232 address

1…247

(1)

Identifies the device on the link. 0 is typically used
by the DF1 master. 255 is the broadcast address

6

40407

Data format

0…2

0

Parity, number of data bits, number of stop bits
0 = No parity, 8 data bits, 1 stop bit
1 = Even parity, 8 data bits, 1 stop bit
2 = Odd parity, 8 data bits, 1 stop bit

7

40408

Flow Control (Handshaking)

0…1

0

Data flow control for RS-232/RS-485 port.
0 = None
1 = Hardware RTS/CTS

8

40409

RTS On Delay

0…9995
ms

0

9

40410

10

40411

Inter-character timeout

Specifies the minimum delay between characters
that indicates the end of a message packet. 0 = 3.5
character times.

11

40412

Error checking

0…1

0

0 = CRC
1 = BCC