Configuring the time-of-use log – Rockwell Automation 1404-M4_M5_M6_M8 Powermonitor 3000 User Manual, Firmware rev. 3.0 or LATER User Manual

Page 157

Advertising
background image

Publication 1404-UM001F-EN-P - November 2009

157

Data Logging Chapter 7

Configuring the Time-of-use Log

Perform a table write to the

Time of Use Register Configuration

table

to set up the user-selectable options.

This read/write table of 10 integer elements contains the following
configuration and read-back selection parameters.

Passwordrequired for configuration. Use a valid password or
-1 for read-back select. Range 0…9999, default 0, returns -1

Record to read backselects the record to be returned in the
next read of the Tables

Time of Use Records – Real Energy and

Demand

,

Time of Use Records – Reactive Energy and Demand

,

and

Time of Use Records – Apparent Energy and Demand

.

Range 0…12, default 0

Write commandstores record 0 to record 1 and shifts
remaining records down. Range 0 (no action), 1 (execute write
command), default 0

Log dayselects the day of the month to automatically store the
in-process record and shift the remaining records down. Range 0
to 31. 0 disables automatic store. 1…28 select the day of month,
29…31 select last day of month

Off-peak dayselects day(s) of week during which all hours are
off-peak. Bitfield, bit 0 = Sunday, bit 1 = Monday and so on.
Range 0…127 (0…FF Hex), default 65 (41 Hex, Saturday and
Sunday)

Mid peak AM selects morning mid peak time-of-use hours.
Bitfield, range 0…4095 (0 to 0FFF hex). See Time-of-use
selection above. Default 1792 (700 Hex, 8:00 to 10:59 a.m.)

TOU Period

AM

PM

12:0

0 – 12:59

1:00

– 1:59

2:00

– 2:59

3:00

– 3:59

4:00

– 4:59

5:00

– 5:59

6:00

– 6:59

7:00

– 7:59

8:00

– 8:59

9:00

– 9:59

10:0

0 – 10:59

11:0

0 – 11:59

12:0

0 – 12:59

1:00

– 1:59

2:00

– 2:59

3:00

– 3:59

4:00

– 4:59

5:00

– 5:59

6:00

– 6:59

7:00

– 7:59

8:00

– 8:59

9:00

– 9:59

10:0

0 – 10:59

11:0

0 – 11:59

Peak

0

0

0

0

0

0

0

0

0

0

0

1

1

1

1

0

0

0

0

0

0

0

0

0

Mid peak

0

0

0

0

0

0

0

0

1

1

1

X

(1)

X

X

X

1

1

1

1

0

0

0

0

0

(1)

x = Don’t care.

Advertising