Chapter 3 Powermonitor 3000 Unit Operations

Power Results

Real power, that is the portion of the voltage and current applied to a
power system that is doing work, is calculated on a per-phase (L1 Real
Power, L2 Real Power, L3 Real Power), and Total Real Power. L1
Reactive Power, L2 Reactive Power, L3 Reactive Power and Total
Reactive Power similarly return that portion of the power used in
capacitive or inductive reactance in the power system and doing no
work. L1 Apparent Power, L2 Apparent Power, L3 Apparent Power
and Total Apparent Power return the apparent power, which is the
simple mathematical product of the system voltage and system
current.

For single-phase wiring mode, all L3 power values remain at zero and
are not included in the total power calculation.

Voltage, Current, and Frequency Metering

Parameter

Description

Range

Units

Phase 1 L-N Voltage

RMS line to neutral voltage of individual phase or three-phase
average

0…999.9x10

22

Volts

Phase 2 L-N Voltage
Phase 3 L-N Voltage
3-Phase Average L-N Voltage
Phase 1 L-L Voltage

RMS line to line voltage of individual phase or three-phase
average

0…999.9x10

22

Volts

Phase 2 L-L Voltage
Phase 3 L-L Voltage
3-Phase L-L Voltage
Phase 1 Current

RMS line current in individual phase or three-phase average

0…999.9x10

22

Amps

Phase 2 Current
Phase 3 Current
3-Phase Average Current
Phase 4 (Neutral) Current

RMS current of phase 4, also known as neutral or zero-sequence
current

0…999.9x10

22

Amps

Frequency

The frequency of the voltage

40.0…75.0

Hertz

Phase Rotation

The phase rotation of a three-phase system

None
ABC
ACB

N/A

Voltage Positive Sequence

Magnitude of positive sequence voltage in a three-phase
system

(1)

0…999.9x10

22

Volts

Voltage Negative Sequence

Magnitude of negative sequence voltage in a three-phase
system

(1)

0…999.9x10

22

Volts

Current Positive Sequence

Magnitude of positive sequence current in a three-phase system

0…999.9x10

22

Amps

Current Negative Sequence

Magnitude of negative sequence current in a three-phase system 0…999.9x10

22

Amps

Voltage Unbalance

The ratio between the negative and positive voltage sequence in
a three-phase system

0…100 Percent

Current Unbalance

The ratio between the negative and positive current sequence in
a three-phase system

0…100 Percent

(1)

Expressed in line-to-neutral volts for Wye and line-to-line volts for Delta wiring modes.